Network floor

Specifications and Pefformance

Specifications

Network floor 40

Concrete Mat Base Mat 40 Feed-In Mat 40 Border Mat 40
Material High-strength lightweight concrete and molded PVC sheeting
Size 40(H) × 600(W) × 600(L)mm
Effective Cabling
Space per Mat
(600mm)
36(H)×70(W)×2
Channels
= 5,040mm2 per mat
36(H)×125(W)×3
Channels
= 13,500mm2 per mat
20(H)×15(W)×12
Channels
= 3,600mm2 per mat
Distance Between
Cable Paths
300 mm 200 mm 50 mm
Cable Path Cover
Center Cover Straight Cover
Material Steel plate with lead-free cation coating
Size 2.3(t)×147(W)×147(L)mm 2.3(t)×98.5(W)×147(L)mm

Network floor 29

Concrete Mat Base Mat 29 Feed-In Mat 29 Border Mat 29
Material High-strength lightweight concrete and molded PVC sheeting
Size 29(H) × 600(W) × 600(L)mm
Effective Cabling
Space per Mat
(600mm)
25(H)×70(W)×1
Channels
= 1,750mm2 per mat
25(H)×125(W)×3
Channels
= 9,375mm2 per mat
14(H)×15(W)×12
Channels
= 2,520mm2 per mat
Distance Between
Cable Paths
600 mm 200 mm 50 mm
Cable Path Cover
Center Cover Straight Cover
Material Steel plate with lead-free cation coating
Size 2.3(t)×197(W)×197(L)mm 2.3(t)×98.5(W)×197(L)mm

Network floor 40 Plus

Concrete Mat Base Mat 40Plus Feed-In Mat 40 Border Mat 40
Material High-strength lightweight concrete and molded PVC sheeting
Size 40(H) × 600(W) × 600(L)mm
Effective Cabling
Space per Mat
(600mm)
36(H)×70(W)×1
Channels
= 2,520mm2 per mat
36(H)×125(W)×3
Channels
= 13,500mm2 per mat
20(H)×15(W)×12
Channels
= 3,600mm2 per mat
Distance Between
Cable Paths
600 mm 200 mm 50 mm
Cable Path Cover
Center Cover Straight Cover
Material Steel plate with lead-free cation coating
Size 2.3(t)×147(W)×147(L)mm 2.3(t)×98.5(W)×147(L)mm

Performance

Weight "NWF40" : 30kg/m2
"NWF29" : 26kg/m2
"NWF40Plus" : 33kg/m2 (with cable path cover)
Load Endurance
  1. Concrete mat : 5000N (≒510kgf/50mm dia)
  2. Cable path cover : 3000N (≒306kgf/50mm dia)
Rolling Load Endurance
  1. Assuming a cart load of 300kg(75kg per wheel of hard synthetic rubber)
    : Capable of withstanding 250,000 passes.
  2. Assuming a chair load of 80kg (20kg per wheel)
    : Capable of withstanding 1,000,000 passes.
Resistance to Uniformly Distributed Load
  1. Concrete mat : 10 ton/200mm×200mm
  2. Cable path cover : 5 ton/200mm×200mm (Tested withe Load Bearing Plate: t10mm, 200x200mm.) Item No. (PW0622)
Fire Resistance
  1. British Standard Compliant : Class 2 (top rating) for BS476: Part4
    (Non-combustibility test for materials)
  2. Japanese Standard Compliant : Certification No. 61002, having passed the surface test for quasi-noncombustible materials and the test of hazardous gas emissions, specified in the Ministry of Construction's announcement no.1231 of 1976.
Impact Endurance
  1. Assuming natural falling of a 30kg sand bag from 0.25m height
    : No change in impact endurance.
Vibration and Impact Strength Assuming a mobile library with a 2 ton live load moves back and forth
: Capable of withstanding 250,000 passes of forward and backward movement.
Certification Public Building Association and Good Design Award.